Service Manual

13
3. UF/WF: Freezer
UF/WF - Freezer Sequence Flow Chart
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DLT-defrost lock-out timer
DT-defrost timer
DTh-defrost thermistor
EvapFM-evaporator fan motor
FDD-fan delay after defrost
MH-mullion heater
PH-perimeter heater
1. Startup/Cool Down
2. Cool Down Achieved
Comp energized
ConFM energized
EvapFM energized
MH energized
PH energized
5-hr. DT starts
CTh in control
4. Defrost
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
5. Defrost Termination
DTh in control
Defrost Termination:
55°F (°12.7C) achieved or
1 hr. backup defrost timer
terminated.
1-hr. DLT terminates
5-hr. DT terminates or
Evap. temp. at or below -31°F (-35°C)
5-min. minimum DT starts
1-hr. maximum DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
Note:
a) 2-min. minimum Comp on timer starts when Comp energizes
b) 3-min. minimum Comp off timer starts when Comp de-energizes
c) 5-min. minimum defrost time
d) 1-hr. maximum defrost time
e) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT))
f) 1-hr. defrost lock-out time after defrost terminated (DLT)
g) 3-min. EvapFM delay timer terminates or DTh reaches 10°F (-12°C) (FDD (fan delay after defrost), then evaporator fan motor energizes.
*
3-min. DOT terminates or
Evap Temp. Achieves
10°F (-12°C) (FDD)
1-hr. DLT starts
5-hr. DT starts
EvapFM energized
*
Evap. Temp. achieves
55°F (12.7°C) or
1-hr. DT terminates
DH de-energized
3-min. DOT starts
Comp energized
ConFM energized
MH energized
PH energized
3. Cool Down Restarts
CTh above setpoint CTh cools to setpoint
CTh above
setpoint
*
*
*
* *
*
*
Power on
Yellow LED On
(10-sec. Delay)
Red, Yellow, and
Green LEDs Cycle
Red and Green LEDs on
Yellow LED off
Green LED on
Red and Yellow LEDs off
*
*
Defrost: Temperature or
Time achieved.
DTh achieves -31°F(-35°C)
or 5-hr. DT terminates
5-min. minimum and
1-hr. maximum DT starts
6. Drip Off Time
3-min DOT
Terminates
*