3. Defrost
UR/WR Defrost - Possible Cause
1. Control Module (fails to initiate)
See "II.C. Control Module Check"
a) Defective-Cumulative 5-hr. defrost timer fails.
b) Defective-1-hr. defrost lock-out timer fails.
2. Control Module (fails to terminate)
See "II.C. Control Module Check"
a) Defrost thermistor connection loose.
b) Defective.
3. Defrost Thermistor (Conrm DTh
status. See "II.D. Thermistor Check")
a) Defective.
SR and UF/WF Defrost - Possible Cause
1. Control Module (fails to initiate)
See "II.C. Control Module Check"
a) Defective (Cumulative 5-hr. defrost timer fails).
2.
Defrost Safety Thermostat
a)
Defective. Open. Cut-out: 120°F±5°F (49°C±3°C), Cut-in: 70°F±5°F
(21°C±3°C).
3.
Defrost Heater
a)
Defrost safety thermostat open.
b)
Defective.
4. Defrost Thermistor (Conrm DTh
status. See "II.D. Thermistor Check")
a) Defective.
5. Control Module (fails to terminate)
See "II.C. Control Module Check"
a) Defrost thermistor connection loose.