Instruction Manual

Table 32 Environmental operating specications
Ambient temperature : +1Cto+3C(+5Fto+9F)withan
averagerateofchangeof1°C/hourmaximumandastepchangeof3°C
or less. Maintaini
ng the optimum ambient temperature within the specied
range ensures that
the internal operating temperatures support the drive
manufacturer’s MTBF specications.
Relative humidity: 40%to60%(noncondensing)withastepchangeof10%
or less (noncondensing)
Air quality: Not to exceed a max imum of 500,000 particles, 0. 5 micron or
larger, per cubic foot of air.
Heat dissipatio
n: 160 0 BT Us p e r h ou r
When shipping, o
r placing this product in short term storage, HP recommends maintaining the
environmental conditions listed in Table 33.
Table 33 Environmental shipp in g or sh ort-term stora ge s pecications
Ambient temperature
: –40 °C to +66 °C (–40 °F to +151 °F)
Relative humidity: 10% to 80% noncondensing
Altitude: below 15,240 m (50,000 ft)
Power specication
s
The input voltage to the drive enclosure power supplies is a function of the country-specicinputvoltage
to Enterprise storage system rack power distribution units (PDUs) . Table 34 denes the AC input power
available to the dr
ive enclosure power supplies.
CAUTION:
The AC power distribution within a rack ensures a balanced to each PDA and reduces the possibilit y of
an overload condition. Changing the cabling to or from a PDM could cause an overload condition.
Table 34 Enterprise storage system AC input line voltages
Specication
Minimal Nominal
Maximum
60 Hz Service
AC Line Voltage
57 Hz
60 Hz 63 Hz
AC Line Voltage—Japan
180 V AC 202 V AC 220 VAC
AC Line VoltageNorth America
180 V AC 208 VAC 220 VAC
AC Line VoltageEurope
208VAC 240VAC 254VAC
50 Hz Service
AC Line Frequency 47 Hz
50 Hz 53 Hz
AC Line Voltage–Japan
180 V AC 202 V AC 220 VAC
AC Line VoltageNorth America
190 V AC 220 VAC 235 V AC
AC Line VoltageNorth America
200 VAC 230 V AC 2 44 V AC
AC Line VoltageEurope
208VAC 240VAC 254VAC
Table 35 denes the AC input current and wattage to the d rive enclosure power supplies.