Regulatory Notices and Specifications
152 Enterprise Virtual Array 3000 User Guide
Caution: The AC power distribution within a rack ensures a balanced load to
each PDU and reduces the possibility of an overload condition. Changing the
cabling to or from a PDM could cause an overload condition.
Table 31 defines the AC input current and wattage to the power supplies.
Table 30: Enterprise Storage System AC Input Line Voltages
Specification Minimal Nominal Maximum
60 Hz Service
AC Line Frequency 57 Hz
60 Hz 63 Hz
AC Line Voltage–Japan 180 VAC
202 VAC 220 VAC
AC Line Voltage–North America 180 VAC
208 VAC 220 VAC
AC Line Voltage–Europe 208 VAC
240 VAC 254 VAC
50 Hz Service
AC Line Frequency 47 Hz
50 Hz 53 Hz
AC Line Voltage–Japan 180 VAC
202 VAC 220 VAC
AC Line Voltage–North America 190 VAC
220 VAC 235 VAC
AC Line Voltage–North America 200 VAC
230 VAC 244 VAC
AC Line Voltage–Europe 208 VAC
240 VAC 254 VAC
Table 31: AC Input Current and Wattage
Nominal Maximum
Input Voltage Amps Watts Amps Watts
60-Hz Input
100 VAC–JBOD 4.35 436 6.41 641
208 VAC–North America 2.03 419 2.94 609
50-Hz Input
120 VAC–JBOD 3.59 419 5.27 633
220 VAC–North America 1.92 418 2.78 608
230 VACNorth America 1.92 418 2.78 608
240 VAC–Europe 1.76 416 2.55 607