EMU Generated Condition Reports
165Enterprise Virtual Array 3000 User Guide
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Replace the defective drive with:
A Fibre-Channel-compatible drive.
A Fibre Channel drive capable of operating at a link rate supported by I/O
modules and transceivers.
3. Observe the EMU to ensure the error is corrected.
4. If unable to correct the problem, contact your HP authorized service
representative.
0.1.en.02 INFORMATION ConditionDrive Missing
The drive is improperly installed or missing. Either option could affect the
enclosure air flow and cause an overtemperature condition for another element.
This error remains active for 1 minute, or until the problem is corrected,
whichever occurs first.
Immediate correction is not required. However, correction cannot be delayed
indefinitely.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Remove and install the drive to ensure that it is properly installed.
3. Observe the EMU to ensure the error is corrected.
4. If removing and installing the drive did not correct the problem, install a
replacement drive or a drive blank.
5. Observe the EMU to ensure the error is corrected.
6. If unable to correct the problem, contact your HP authorized service
representative.
0.1.en.03 INFORMATION ConditionDrive Software Lock Active
Some enclosures have a software-activated lock that prevents physically removing
a drive while this feature is active. This feature can be activated even when an
enclosure does not have a physical lock. Removing a drive when this feature is
active generates a condition report. This error remains active for 15 seconds.
No action is required to correct this condition.