166 Enterprise Virtual Array 3000 User Guide
0.1.en.04 CRITICAL ConditionLoop A Drive Link Rate Incorrect
The drive is capable of operating at the loop link rate, but is running at a different
rate. For example, the drive is operating at 1 Gbps, and the loop is operating at
2 Gbps. Only when the drive is operating at the Fibre Channel link rate
established by the I/O module can this drive transfer data.
This error remains active until the problem is corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Remove and replace the drive in the enclosure.
3. Observe the drive status LEDs to ensure the drive is operational.
4. Observe the EMU to ensure the error is corrected.
5. If removing and replacing the drive did not correct the problem, replace the
drive.
6. Observe the drive status LEDs to ensure the drive is operational.
7. Observe the EMU to ensure the error is corrected.
8. If unable to correct the problem, contact your HP authorized service
representative.
0.1.en.05 CRITICAL ConditionLoop B Drive Link Rate Incorrect
The drive is capable of operating at the loop link rate but is running at a different
rate. For example, the drive is operating at 1 Gbps, and the loop is operating at
2 Gbps. Only when the drive is operating at the Fibre Channel link rate
established by the I/O module can this drive transfer data.
This error remains active until the problem is corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Remove and replace the drive in the enclosure.
3. Observe the drive status LEDs to ensure the drive is operational.
4. Observe the EMU to ensure the error is corrected.
5. If removing and replacing the drive did not correct the problem, replace the
drive.
6. Observe the drive status LEDs to ensure the drive is operational.