EMU Generated Condition Reports
172 Enterprise Virtual Array 3000 User Guide
Temperature Conditions
The format of a temperature condition report is 0.4.en.ec, where:
0.4. is temperature sensor element type
en. is the two-character temperature sensor element
ec is the error code
Refer to Table 44 to determine the location of each temperature sensor.
The following sections list the temperature condition reports and the default
temperature thresholds. Use Command View EVA to view the temperature sensor
ranges for the disk drives, EMU, and power supplies.
0.4.en.01 NONCRITICAL ConditionHigh Temperature
This condition report indicates that an element temperature is approaching, but
has not reached, the high temperature CRITICAL threshold. Continued operation
under these conditions may result in a CRITICAL condition. This condition report
remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Ensure that all elements are properly installed to maintain proper air flow.
3. Ensure that nothing is obstructing the air flow at either the front of the
enclosure or the rear of the blower.
Table 44: Temperature Sensor Element Numbering
Sensor Sensor Location Sensor Sensor Location
01. Power Supply 1 Exhaust 10. Drive Bay 7
02. Power Supply 2 Exhaust 11. Drive Bay 8
03. EMU 12. Drive Bay 9
04. Drive Bay 1 13. Drive Bay -
05. Drive Bay 2 14. Drive Bay q
06. Drive Bay 3 15. drive Bay w
07. Drive Bay 4 16. Drive Bay e
08. Drive Bay 5 17. Drive Bay r
09. Drive Bay 6