4.6
3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual
When placing cabinets with their weight shared by the same panels as shown in Figure 4-2 on
page 4.5, verify that each panel can tolerate the maximum weight per panel, calculated as
follows:
where cabinet x and cabinet y are cabinets or equipment resting partially on the same floor
panel.
4.3.3 Weight and Pressure Loads
Depending on the configuration, an InServ Storage Server can weigh up to 2,000 lb (907 kg).
Figure 4-2 provides maximum weights and pressure loads per leveling foot for 3PAR cabinets.
Use these values to approximate the structural support required by a storage server cabinet.
weight cabinet x + weight cabinet y
2
Table 4-2. Maximum Weights and Pressure Loads
Cabinet
Size
Maximum
Weight
Maximum Weight Per
Leveling Foot
Maximum Load
Per Leveling Foot
1M
(20U)
682 lbs.
(309.3 kg)
170.5 lbs.
(77.3 kg)
no levelers
2M (40U) 1,069 lbs.
(484.8 kg)
267.25 lbs.
(121.2 kg)
87.4 lb/sq in.