Reference Guide

5.8
3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual
Max. BTUs/hour per cabinet (fully
populated)
9,825
Input Voltage (VAC) (200 - 240)
Frequency (Hz) (50 - 60), 1-phase 50/60
Circuit Breaker Max 30 amps per PDU (de-rated to 24 amps)
Power Connectors (provided) (2) L6-30P for 1+1 redundancy
2 Meter Cabinet
Max. Watts per Cabinet (fully populated)
*
5,580
Max. BTUs/hour per cabinet (fully
populated)
19,040
Input Voltage (VAC) (200 - 240)
Frequency (Hz) (50 - 60), 1-phase
Circuit Breaker Max 30 amps per PDU (de-rated to 24 amps)
Power Connectors (provided) (4) L6-30P for 1+1 rdnt.
E200 Controller Node Chassis
Watts 730
BTUs/hour (fully populated) 2491 BTUs/hr.
Input Voltage 100-240 VAC
Frequency 50-60 Hz
Power Receptacle IEC-320 for 1+1 redundancy. (2 for 1
Meter and 4 for 2 Meter)
F200 Controller Node Chassis (Dual Node)
Table 5-1. Power and Heat Specifications (continued)