0.7.01.17 UNRECOVERABLE condition—Power shutdown failure
The power supply did not respond to a controller, EMU, or power supply shut down command.
Shutting down the supply is required to prevent overheating.
Complete the following procedure to correct the problem:
1. Record all six characters of the condition report.
2. Move the power cord bail lock 1, Figure 42 (page 128), to the left.
3. Disconnect the AC power cord 2 from the supply.
Figure 42 Disconnecting AC power
0.7.01.18 UNRECOVERABLE condition—EMU hardware failure
The EMU has detected an internal hardware problem. This condition report remains active until
the problem is corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Reset the EMU.
3. Observe the EMU to ensure the error does not recur within the first minute.
4. If the error does recur, contact your HP authorized service representative. The EMU is
inoperative and must be replaced as soon as possible.
0.7.01.19 UNRECOVERABLE condition—EMU ESI driver failure
The EMU has detected an internal hardware problem. This condition report remains active until
the problem is corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Reset the EMU.
3. Observe the EMU to ensure the error does not recur within the first minute.
4. If the error does recur, contact your HP authorized service representative. The EMU is
inoperative and must be replaced as soon as possible.
Transceiver conditions
The format of a transceiver condition report is 0.F.en.ec, where:
0.F. is the transceiver element type number
en. is the two-character transceiver element number (see Figure 43 (page 129))
ec is the error code
128 EMU-generated condition reports