Table 36 EVA4x00 power specifications 208 Volts
2C4D2C3D2C2D2C1DSpecification
176713901013638Total System WattageTypical
1
5585430030141729Total System BTU/hour
4.43.52.61.6Input Current (A) -
Typical per line
22017013298In Rush Current (A)
7.55.94.32.7Input Current (A) -
Maximum per line
Failover Mode
1
Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly. For
example, if you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM
drives.
Table 37 EVA4x00 power specifications 230 Volts
2C4D2C3D2C2D2C1DSpecification
176713901013638Total System
Wattage
Typical
1
5585430030141729Total System
BTU/hour
4.23.32.41.5Input Current (A) -
Typical per line
244190147104In Rush Current (A)
7.15.54.12.6Input Current (A) -
Maximum per line
Failover Mode
1
Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly. For
example, if you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM
drives.
Table 38 EVA6x00 power specifications 208 Volts
2C8D2C7D2C6D2C5D2C4DSpecification
33442967259022141837Total System
Wattage
Typical
1
1140910124883875536268Total System
BTU/hour
8.47.46.55.54.6Input Current (A) -
Typical per line
363321280250220In Rush Current (A)
14.212.611.09.47.8Input Current (A) -
Maximum per line
Failover Mode
1
Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).