User's Manual

Table 49 100V Wattage and BTU/Hour
EVA8x00EVA6x00EVA4x00Enclosures
BTU/hWattsVAAmpsBTU/hWattsVAAmpsBTU/hWattsVAAmps
EVA8x00 not supported
118553474354535.58
105183082314531.57
91812691274627.56
78452299234623.55
65081907194619.562691837187518.74
51711516154615.549331446147514.83
38351124114711.535961054107510.82
24987327477.522596626766.81
UPS Selection
This section provides information that can be used when selecting a UPS for use with the EVA. The
four HP UPS products listed in Table 50 (page 141) are available for use with the EVA and are
included in this comparison. Table 51 (page 141) identifies the amount of time each UPS can sustain
power under varying loads and with various UPS ERM (Extended Runtime Module) options.
The load imposed on the UPS for different disk enclosure configurations are listed in Table 52 (page
142), Table 53 (page 142), and Table 54 (page 143).
NOTE: The specified power requirements reflect fully loaded enclosures (14 disks) .
Table 50 HP UPS models and capacities
Capacity (in watts)UPS Model
1340R1500
2700R3000
4500R5500
12000R12000
Table 51 UPS operating time limits
Minutes of operation
Load (percent)
With 2 ERMsWith 1 ERMWith standby battery
R1500
49235100
6332680
161571350
2901463420
R3000
205100
306.580
451250
1204020
Environmental and operating specifications 141