TECO – Westinghouse Motor Company Serial Communications Modbus 118
Data format [16] Operating state:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
BUSY WR RL ALM DEC ACC IL VL TL NUV BRK INT EXT REV FWD
(All bit are ON or active by 1)
FWD: Forward operation IL: Current limiting
REV: Reverse operation ACC: Under acceleration
EXT: DC braking active (or pre-excitation) DEC: Under deceleration
ALM: Inverter fault
INT: No Output RL: Transmission valid
BRK: Braking active WR: Function writing privilege
NUV: DC link voltage is established 0: Keypad panel
(undervoltage at 0) 1: RS-485
TL: Torque limiting 2: Fieldbus (option)
VL: Voltage limiting BUSY: Processing data write
Data format [17] Type code:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Type Generation Series Voltage series
Code Type Generation Series Voltage series
1 - EQ5 - -
2 - - - -
3 EQ5 - - 230V three phase
4 - - - 460V three phase
5 - - USA 575V three phase
6 - - - -
Data format [18] Code setting (14 figures):
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Data 4 Data 3 Data 2 Data 1
Data format [19] Amperage value Decimal data (positive ):
Min. unit 0.01 inverter capacity is not more than 30HP/CT, 40HP/VT.
Min unit 0.01 for not less than 40HP/CT, 50HP/CT.
Example: F11 (electronics thermal overload relay 1 level) 107.0A (40HP) 107.0 X 10=1070=042E
H
F11 (electronics thermal overload relay 1 level) =3.60A (1HP) 3.60 X 100=360=0168
H