HP StorageWorks ESL9000 Series Pass-Through Mechanism (PTM) Installation Guide (February 2005)

Installing a PTM
35HP StorageWorks ESL9000 Series Pass-Through Mechanism (PTM) Installation Guide
Installing the PTM adapter plate
To install the PTM adapter plate:
1. Remove the cable hole plug as shown in Figure 12 and install the bushing
provided into the hole.
Note: Two sizes of bushing were provided with the upgrade kit: 1.5 in. (0605061) and 2
in. (0605060). Use the bushing that best fits the cable hole.
Figure 12: PTM cable routing
2. Reach through the hole (see Figure 12) and pull the pass-through cable
through the hole, leaving approximately 18 in. of cable on the front side of the
bin wall.
3. Install the PTM adapter plate, securing it with the six screws provided in the
PTM kit (see Figure 12).
4. Attach the pass-through cable cover with three nylon push-in clips and four
10-32 x 5/8 screws and washers to the bin wall to cover the cable and cable
hole, ensuring that the PTM cable is routed correctly under the raised channel
in the cover (see Figure 13). Tighten screws to 30 ± 3 in lb.
5. Install the bin shelf openings cover using six nylon push-in clips (see
Figure 13).
1 PTM adapter plate
2 Bushing
3 PTM cable
123