HP StorageWorks ESL9000 Series Pass-Through Mechanism (PTM) Installation Guide (February 2005)

Installing a PTM
39HP StorageWorks ESL9000 Series Pass-Through Mechanism (PTM) Installation Guide
Centering the PTM assembly
After the PTM assembly has been installed in the libraries, it must be centered to
operate correctly. For ESL9198 and ESL9322 libraries, center the PTM between
the libraries inside the walls as shown in Figure 16. The distance between the
inside wall and the PTM in the left library 1 and the distance between the inside
wall and the PTM in the right library 2 should be 14.06 +
0.06 inches in an
ESL9198 and 16.60 +
0.06 inches in an ESL9322.
Figure 16: Centering the PTM (ESL9198 shown)
14.60 (ESL9198)
1
14.60 (ESL9198)
2
16.60 (ESL9322)
16.60 (ESL9322)
Inside Wall