HP StorageWorks ESL9000 Series Pass-Through Mechanism (PTM) Installation Guide (February 2005)

67HP StorageWorks ESL9000 Series Pass-Through Mechanism (PTM) Installation Guide
3
Configuring and Calibrating a
PTM
After the PTM has been successfully installed, the libraries must be configured
and calibrated to operate correctly as a multi-unit library system.
Caution: If any library is to utilize Multi-Unit (MUSL) functionality, all libraries
must be running firmware 3.10 or later. In order to utilize MUSL functionality,
all libraries must have the proper backplanes (PN 6310520-04 or newer),
proper robotic controller boards (PN 6221710-21 or newer) and QSPI cables.
All libraries running firmware 1.30 or earlier that upgrade to 3.10 or later that
will utilize MUSL functionality with another library must reinitialize NV RAM
and use the new memory module (PN 6312910-06). To support the new
memory module, boot block version 2.01 must be installed. If a library is
configured in Single mode, then there is no need to upgrade the boot block or
memory module, but the NV RAM must still be reinitialized.
Ensure you understand the capabilities of your application software before
enabling autoclean. If the tape drive autoclean feature is to be supported, be
sure that at least one cleaning tape exists in each library that will support
autocleaning.