- HP 10000 G2 Series Rack Options Installation Guide

Rack Air Duct kit 101
6.
Apply the foam gasketing to the top of the upper duct by peeling the adhesive backing and aligning the
gasketing with the top edges of the upper duct.
Installing the kit assembly
WARNING: The rack air duct weighs approximately 22.5 kg (50 lb). To reduce the risk of
personal injury or damage to the equipment:
Observe local occupational health and safety requirements and guidelines for manual
material handling.
Use at least two people to lift and stabilize the product during installation or removal.
Use step stools to install the product to the top of the rack. Do not lift the air duct over your
head.
1. Using a T-30 Torx screwdriver, remove the two rear M-12 bolts from the top plate of the rack. Retain the
bolts for future use.
2. Align the open slots of the lower air duct to the mounting holes on the top of the rack.
3. Slide the air duct toward the front of the rack, until the front edge slides under the metal slots on the top
plate of the rack (1).
NOTE: You might need to slightly raise the upper duct to access the bolts.
4. Using an adjustable wrench, insert and tighten two M-10 bolts through the holes of the air duct
assembly and into the cage nut holes on top the side assemblies (2).