- HP 10000 G2 Series Rack Options Installation Guide

Airflow Optimization kit 17
Airflow Optimization kit
About this device
The HP Airflow Optimization kit enables you to install foam rail gaskets in your HP 10000 G2 Series 22U,
36U, 42U, and 47U 600-mm (24-in) wide racks and in to 42U 800-mm (31-in) wide racks to improve
separation between hot and cold aisles in the data center.
Kit contents
Item Quantity
600-mm (24-in) perforated floor
gasket
or
800-mm (31-in) perforated floor
gasket
1
1
Foam rail gasket roll
4
Extra hardware might be included for your convenience.
Required tools
No tools are required for this procedure.
Installing foam rail gaskets
IMPORTANT: This option kit is only compatible with HP racks that are 600-mm (24 in) or
800-mm (31 in) wide.
1. Cut the foam rail gasket to fit the size of your rack.
2. Insert the foam rail gasket into the rack front door on both sides of the rack.