3PAR InFormĀ® OS 2.2.4 Messages and Operator's Guide (320-200119 Rev A, March 2009)

10.4
Powering On the Storage Server
InForm OS Version 2.2.4
3PAR Confidential
Figure 10-4. InServ E-Class Hot-Plug LED and Node Status LED
10 From the spmaint main menu:
a Select option 1, SP Control/Status.
b Select option 3, Halt SP and confirm all prompts to halt the SP.
11 Verify that the power LED on the front of the service processor is no longer illuminated.
12 Remove AC to the storage server by turning off the PDU circuit breakers of ALL four PDUs
in the cabinet (Figure 10-5).
Figure 10-5. PDU Circuit Breakers
10.2Powering On the Storage Server
1 Turn on AC power to the cabinet(s) by turning on all the PDU circuit breakers (Figure 10-5)
of ALL four PDUs.
0361_L_R1
Status LED
Hot-Plug LED
0295_L_R2
Circuit Breaker CB-1 Circuit Breaker CB-2
NOTE: The system takes approximately five minutes to become fully operational
providing it was gracefully shut down. If the system was powered off abruptly,
powering on could take considerably longer.