HP 3PAR InForm OS 3.1.1 Messages and Operators Guide
the temperature continues to exceed the limit, contact your local service provider for technical
support and services.
• If a voltage limit has been exceeded, contact your local service provider for technical support
and services.
If the temperature continues to exceed the limit, replace the node.
STATE 6
Node Offline Due to Failure
SUGGESTED ACTION
If the node doesn't come back up within 1 hour, contact technical support.
STATE 7
Node Shutdown Manually
SUGGESTED ACTION
If the node doesn't come back up after maintenance has been completed, contact technical support.
STATE 8
Node MCU is down
SUGGESTED ACTION
It is critical that you replace the node as soon as possible. Run the shownode —mcu
(node-number) to confirm that the MCU is dead. A dash (-) will appear under all columns in
the command output if the MCU is dead.
STATE 9
Node Fan Module 0 Not Present
SUGGESTED ACTION
Contact your local service provider for technical support and services.
STATE 10
Node Fan Module 1 Not Present
SUGGESTED ACTION
Contact your local service provider for technical support and services.
175