Table 3 Raised Floor Specifications
ValueSpecification
-Flatness tolerance
Less than 0.06 in. (1.5 mm)Per 10 ft (3 m) span
Less than 0 .10 in. (2.5 mm)Overall
-Deflection
Less than 0.15 in. (3.8 mm)Dynamic
Less than 0.02 in. (0.5 mm)Permanent
-Pedestal assembly load
At least 5,000 lb (2,268 kg)Axial
At least 30 ft-lb (40.7 N-m)Side
Placing each cabinet across two floor tiles is strongly recommended. It is also strongly recommended
that a vented floor tile be placed in front of each cabinet.
Figure 7 (page 18) shows two storage systems side-by-side, each resting across two floor tiles.
Figure 7 Cabinets Placed Across Two Floor Panels Each (Recommended)
CAUTION: Leave approximately a 1/4 to 3/8 inch space in between each cabinet for proper
clearance to open rear security door.
When necessary, a system can also rest across four floor tiles, with two adjacent storage systems
resting partially on the same tiles and using a total of six tiles, as shown in Figure 8 (page 18).
HP strongly recommends providing vented tiles in the front.
Figure 8 Storage System Resting Partially on the Same Floor Panels
18 Structural/Environmental Considerations