HP 3PAR StoreServ 10000 Storage Physical Planning Manual

the current requirements for a specific system configuration. For proper redundant power protection,
power should be supplied from two or more power sources.
Power and Heat Specifications
NOTE: All measurements listed are based on testing conducted at 208 VAC.
Table 8 Storage System Power Requirements
2 Meter Cabinet
9,984
1
Max. Watts per Cabinet (fully
populated)
34,075Max. BTU/hour per cabinet (fully
populated)
200 watts / 683 BTU/hDrive Chassis (no magazines) Watts
/ BTU/h
Input Voltage (VAC)
220 (200 - 240)Single Phase PDU
200-240 p-p3–Phase PDU (North America)
200-240 p-n; 380-415 p-p3–Phase PDU International)
Frequency (Hz)
50 - 60Single Phase PDU
50-603–Phase PDU (North America)
50-603–Phase PDU International)
Circuit Breaker Max
30 A per PDU (de-rated to 24 A)Single Phase PDU
48 A per PDU (de-rated to 27.71 A
per phase)
3–Phase PDU (North America)
32 A per phase per PDU3–Phase PDU (International)
Power Connectors
(4) L6-30P with 1+1 redundant or (4)
IEC 60309-32A (332P6S) with 1+1
redundant
Single Phase PDU
(2) IEC 309, 3-pole, 4-wire, BLUE, gnd
clocked to 3:00 with 1+1 redundant
3–Phase PDU (North America)
(2) IEC 309, 4-pole, 5-wire, RED, gnd
clocked to 6:00 with 1+1 redundant
3–Phase PDU International)
Power Receptacles
(4) L6-30R with 1+1 redundant or (4)
IEC 60309 with 1+1 redundant
Single Phase PDU
(2) Hubbell HBL460C9W or
equivalent
3–Phase PDU (North America)
(2) Hubbell C532C6S or equivalent3–Phase PDU (International)
Node Pair (fully populated)
IdleTransactional
2
9901315Watts
40 Power Requirements