HP 3PAR StoreServ 7000/7450 Storage Cabling Configuration Guide C: 2 Node Systems with Mixed-Size Drive Enclosures Abstract This guide provides cabling information for authorized technicians performing installation and maintenance services on the HP 3PAR StoreServ 7000/7450 Storage systems.
© Copyright 2013 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. Acknowledgments Microsoft®, Windows®, are U.S.
Contents 1 Cabling Preparation for HP 3PAR StoreServ 7000/7450.................................6 Following Precautions................................................................................................................6 Identifying and Labeling the Components....................................................................................6 2 Cabling HP 3PAR StoreServ 7000/7450.......................................................9 2 Node 2 Drive Enclosures (1S+1L)...........................
Review Completed Cabling...............................................................................................152 2 Node 6 Drive Enclosures (3S+3L)..........................................................................................57 Attach DP-1 Chains to Enclosures........................................................................................150 Attach DP-2 Chains to Enclosures.......................................................................................
2 2 2 2 2 2 2 2 2 2 Attach DP-2 Chains to Enclosures.......................................................................................151 Review Completed Cabling...............................................................................................152 Node 8 Drive Enclosures (6S+2L)........................................................................................113 Attach DP-1 Chains to Enclosures.................................................................................
1 Cabling Preparation for HP 3PAR StoreServ 7000/7450 The following instructions list important precautions and information about cabling installation options for the HP StoreServ Storage system.
Types of Components Use the red and green color coding to assist with the cabling. Only connect to components sharing the same color.
Labeling the Enclosures Before connecting the cables: • Labels (A, B, C, and D) are provided to help identify the enclosures in the storage system. Apply the labels to each enclosure in a visible location and avoid covering other labels • Apply label A to the controller enclosure with nodes 0 and 1. Alternate the labeling (A/B) on each enclosure below the controller enclosure If applicable, a system using four nodes, apply label C to the controller enclosure with nodes 2 and 3.
2 Cabling HP 3PAR StoreServ 7000/7450 The following illustrative sections provide a rear view of the rack with recommended racking configuration of the system. 2 Node 2 Drive Enclosures (1S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 10 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 12 Cabling HP 3PAR StoreServ 7000/7450
2 Node 3 Drive Enclosures (1S+2L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 14 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 16 Cabling HP 3PAR StoreServ 7000/7450
2 Node 3 Drive Enclosures (2S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 18 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 20 Cabling HP 3PAR StoreServ 7000/7450
2 Node 4 Drive Enclosures (1S+3L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 22 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 24 Cabling HP 3PAR StoreServ 7000/7450
2 Node 4 Drive Enclosures (2S+2L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 26 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 28 Cabling HP 3PAR StoreServ 7000/7450
2 Node 4 Drive Enclosures (3S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 30 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 32 Cabling HP 3PAR StoreServ 7000/7450
2 Node 5 Drive Enclosures (1S+4L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 34 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 36 Cabling HP 3PAR StoreServ 7000/7450
2 Node 5 Drive Enclosures (2S+3L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 38 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 40 Cabling HP 3PAR StoreServ 7000/7450
2 Node 5 Drive Enclosures (3S+2L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 42 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 44 Cabling HP 3PAR StoreServ 7000/7450
2 Node 5 Drive Enclosures (4S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 46 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 48 Cabling HP 3PAR StoreServ 7000/7450
2 Node 6 Drive Enclosures (1S+5L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 50 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 52 Cabling HP 3PAR StoreServ 7000/7450
2 Node 6 Drive Enclosures (2S+4L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 54 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 56 Cabling HP 3PAR StoreServ 7000/7450
2 Node 6 Drive Enclosures (3S+3L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 58 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 60 Cabling HP 3PAR StoreServ 7000/7450
2 Node 6 Drive Enclosures (4S+2L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 62 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 64 Cabling HP 3PAR StoreServ 7000/7450
2 Node 6 Drive Enclosures (5S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 66 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 68 Cabling HP 3PAR StoreServ 7000/7450
2 Node 7 Drive Enclosures (1S+6L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 70 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 72 Cabling HP 3PAR StoreServ 7000/7450
2 Node 7 Drive Enclosures (2S+5L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 74 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 76 Cabling HP 3PAR StoreServ 7000/7450
2 Node 7 Drive Enclosures (3S+4L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 78 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 80 Cabling HP 3PAR StoreServ 7000/7450
2 Node 7 Drive Enclosures (4S+3L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 82 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 84 Cabling HP 3PAR StoreServ 7000/7450
2 Node 7 Drive Enclosures (5S+2L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 86 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 88 Cabling HP 3PAR StoreServ 7000/7450
2 Node 7 Drive Enclosures (6S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 90 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 92 Cabling HP 3PAR StoreServ 7000/7450
2 Node 8 Drive Enclosures (1S+7L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 94 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 96 Cabling HP 3PAR StoreServ 7000/7450
2 Node 8 Drive Enclosures (2S+6L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 98 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 100 Cabling HP 3PAR StoreServ 7000/7450
2 Node 8 Drive Enclosures (3S+5L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 104 Cabling HP 3PAR StoreServ 7000/7450
2 Node 8 Drive Enclosures (4S+4L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 108 Cabling HP 3PAR StoreServ 7000/7450
2 Node 8 Drive Enclosures (5S+3L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 110 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 112 Cabling HP 3PAR StoreServ 7000/7450
2 Node 8 Drive Enclosures (6S+2L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 114 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 116 Cabling HP 3PAR StoreServ 7000/7450
2 Node 8 Drive Enclosures (7S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 118 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 120 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (1S+8L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 122 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 124 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (2S+7L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 126 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 128 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (3S+6L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 132 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (4S+5L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 134 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all AB drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 136 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (5S+4L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 138 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 140 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (6S+3L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 142 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 144 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (7S+2L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 146 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 148 Cabling HP 3PAR StoreServ 7000/7450
2 Node 9 Drive Enclosures (8S+1L) Before you begin cabling the storage system, carefully read or print the following section, including figures 1 and 2, “Identifying and Labeling the Components” (page 6).
Attach DP-1 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-1) to the I/O 0 (DP-1) on the A drive enclosure closest to the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-1) to I/O 1 (DP-1) on the A drive enclosure farthest from the controller. Connect all A drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: 150 The two adjacent enclosures are not directly connected.
Attach DP-2 Chains to Enclosures Red routing 1. 2. Connect Node 0 (DP-2) to the I/O 0 (DP-1) on the B drive enclosure closest to the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working away from the controller. Green routing 1. 2. Connect Node 1 (DP-2) to I/O 1 (DP-1) on the B drive enclosure farthest from the controller. Connect all B drive enclosures from (DP-2) to (DP-1) working toward the controller. NOTE: The two adjacent enclosures are not directly connected.
Review Completed Cabling 152 Cabling HP 3PAR StoreServ 7000/7450