HP 3PAR StoreServ 7450 Storage Site Planning Manual

Power and Heat Specifications
The following table lists the electrical power requirements.
Table 3 Power Requirements
Transactional (watts/BTU/hr)Idle (watts/BTU/hr)Component
398 W / 1357236 W / 803Node Pair, no drives, no add-on
host adapters
32.6 / 11124 W / 81.724-port 8 Gb/s Fibre Channel
Adapter
40 W / 136.434 W / 115.772-port 10 Gb/s iSCSI/FCoE
Adapter
150 / 512 (average)150 / 512 (average)HP M6710 2.5 inch 2U SAS Drive
Enclosure, no drives
164 / 559 (average)164 / 559 (average)HP M6720 3.5 inch 4U SAS Drive
Enclosure, no drives
3.9 / 13.31.4 / 4.8100 GB SLC SSD
3.9 / 13.31.4 / 4.8200 GB SLC SSD
7.5 / 12.62.2 / 3.7400 GB SLC SSD
5.5 / 18.72.2 / 7.49480 GB SLC SSD
5.2 / 17.82.0 / 6.7920 GB SLC SSD
NOTE: Refer to “Power Requirements” (page 21) for complete details.
Environmental Specifications
The operating site must comply with the following environmental specifications.
Table 4 Environmental Specifications
10,000ft/ 3,024m OperationalAltitude
40,000ft/ 12,192m Shipping
Operating: 41–104° F (5–40° C) - Reduce rating by F for each 1000 ft altitude (1.8°
C/1,000 m)
Temperature
Non–operating: 32–203° F (0–9 C)
32–140° F (0–60° C)Shipping Temperature
10–90% non-condensingHumidity
10–90% non-condensingShipping Humidity
Operating: 0.25 G, Sine, 5-500 Hz; 0.15 Grms Random, 5-100 HzVibration
Non-operating: 0.5G, Sine, 5-500 Hz
Operating: 2 G, 11ms, half-sineShock
Non-operating: 10 G, 11ms, half-sine
For more information, refer to “Structural/Environmental Considerations” (page 17) for details.
Cable Specifications
The following table lists the types of cables commonly required for the installation of a storage
system.
12 System Components and Specifications