R3204P16-HP Load Balancing Module System Management Configuration Guide-6PW101

20
To do…
Use the
command…
Remarks
Set the maximum
number of lines on
the next screen.
screen-length
screen-length
Optional
By default, the next screen displays 24 lines.
A value of 0 disables the function.
Set the size of
history command
buffer
history-command
max-size value
Optional
By default, the buffer saves 10 history commands
at most.
Set the idle-timeout
timer
idle-timeout minutes
[ seconds ]
Optional
The default idle-timeout is 10 minutes. The system
automatically terminates the user’s connection if
there is no information interaction between the
device and the user within the idle-timeout time.
Setting idle-timeout to 0 disables the timer.
CAUTION:
The common settings configured for console login take effect immediately. If you configure the common
settings after you log in through the console port, the current connection may be interrupted, so you should
use another login method. After you configure common settings for console login, you need to modify the
settings on the terminal to make them consistent with those on the device.
Logging in through Telnet
Introduction
The device supports Telnet. You can telnet to the device to remotely manage and maintain it, as shown
in Figure 13.
Figure 13 Telnet login
The following table shows the configuration requirements of Telnet login.
Ob
j
ect Re
q
uirements
Telnet server
Configure the IP address of the management Ethernet interface, and make sure
the Telnet server and client can reach each other.( By default, the IP address of
the management Ethernet interface is 192.168.0.1/24)
Configure the authentication mode and other settings
Telnet client
Run the Telnet client program.
Obtain the IP address of the management Ethernet interface on the server
By default, the device is disabled with the Telnet server and client functions.