Brocade Fabric OS v7.2.0d Release Notes v1.0 February 28, 2014 Document History Document Title Summary of Changes Publication Date Brocade Fabric OS v7.2.0d Release Notes v1.
© 2014 Brocade Communications Systems, Inc. All Rights Reserved. ADX, AnyIO, Brocade, Brocade Assurance, the B-wing symbol, DCX, Fabric OS, ICX, MLX, MyBrocade, OpenScript, VCS, VDX, and Vyatta are registered trademarks, and HyperEdge, The Effortless Network, and The On-Demand Data Center are trademarks of Brocade Communications Systems, Inc., in the United States and/or in other countries. Other brands, products, or service names mentioned may be trademarks of their respective owners.
Contents Overview ...................................................................................................................................................... 5 Resolution of Important Defects ............................................................................................................................. 5 New Hardware Support ...........................................................................................................................................
FCR and Integrated Routing .................................................................................................................................. 33 Forward Error Correction (FEC) ............................................................................................................................. 33 FICON......................................................................................................................................................................
Overview Fabric OS (FOS) v7.2.0d is a patch release based on FOS v7.2.0c. All hardware platforms and features supported in FOS v7.2.0c are also supported in FOS v7.2.0d. This release is FICON qualified. Please refer to the Appendix: Additional Considerations for System z (FICON) Environments section for feature details and notes on deployment in FICON environments. Due to the impact of defect 491192 and 494570, Brocade recommends all customers planning or using FOS v7.2.0a, v7.2.0b, and v7.2.
New Feature Descriptions MAPS (Monitoring and Alerting Policy Suite) FOS v7.2 implements a new easy to use policy based monitoring and alerting suite that proactively monitors the health and performance of the SAN infrastructure to ensure application uptime and availability. Brocade MAPS helps users to uncover potential problems in the SAN fabric quickly, before they cause application performance impacts or costly failures.
minute, send an e-mail notification when the error rate is at five per minute, and fence a port when the error rate exceeds ten per minute. Ability to monitor both sudden failures and gradual degradations MAPS provides the ability to not only detect abnormal conditions but also gradually deteriorating conditions in the switch. For example, if a CRC error counter at a switch port increments suddenly at the rate of five per minute, MAPS can detect and alert the end users about that condition.
Bottleneck Detection integration with MAPS dashboard Bottleneck Detection information is integrated with MAPS dashboard. The “Summary” section of the dashboard shows bottleneck events detected by the Bottleneck Monitor. The “History” section of the dashboard shows entries for bottlenecked ports, including transient bottlenecks that are not detected by the Bottleneck Monitor. This enables users to get at an instant view of the bottlenecked ports in the switch and enables rapid problem resolution.
Flow Generator: Flow generator is a test traffic generator for pre-testing the SAN infrastructure (including internal connections) for robustness before deploying the applications. Allows users to configure a16G FC capable port as a simulated device that can transmit frames at full 16G line rate.
ClearLink Diagnostics: D_Port Enhancements FOS v7.2 adds the following D_Port enhancements: Enhancement to D_Port test results Starting with FOS v7.2 complete results of the D_Port tests will be available on the responder switch as well. Prior to FOS v7.2, D_Port test results on the D_Port responder switch did not include optical and remote loopback test results. Complete results were only available on the D_Port initiator switch. D_Port support between Brocade 16G HBA and Brocade 16G Access Gateway.
FOS v7.2 allows buffer credit assignment even for “normal distance” (regular) E_ports The portCfgEportCredits CLI introduced in FOS v7.2 allows users to perform fine grained performance tuning on normal E_ports by allowing users to specify buffer credits. In FOS v7.2, the portaddess CLI has been enhanced to display an address as user bound when a user has explicitly bound an address to a port. FOS v7.
Optionally Licensed Software Fabric OS v7.2 includes all basic switch and fabric support software, as well as optionally licensed software that is enabled via license keys. Optionally licensed features include: Brocade Ports on Demand—Allows customers to instantly scale the fabric by provisioning additional ports via license key upgrade. (Applies to select models of switches).
Adaptive Networking with QoS—Adaptive Networking provides a rich framework of capability allowing a user to ensure high priority connections obtain the bandwidth necessary for optimum performance, even in congested environments. The QoS SID/DID Prioritization and Ingress Rate Limiting features are the first components of this license option, and are fully available on all 8Gb and 16Gb platforms. Note : With FOS v7.
10GbE FCIP/10G Fibre Channel – This license enables the two 10GbE ports on the FX8-24 and/or the 10G FC capability on FC16-xx blade ports supported on DCX 8510 platforms. On the Brocade 6510, Brocade 6520 this license enables 10G FC ports.
Temporary License Support The following licenses are available in FOS v7.
Supported Switches FOS v7.2 supports the following existing platforms: 300, 5100, 5300, 7800, VA-40FC, Brocade Encryption Switch, DCX, DCX-4S 6505, 6510, 6520, DCX 8510-8, DCX 8510-4 FC16-32, FC16-48, FC8-32E, FC8-48E, FX8-24, FS8-18 on DCX 8510-8/DCX 8510-4 FC8-16, FC8-32, FC8-48, FC8-64, FX8-24, FS8-18, FCOE10-24 on DCX/DCX-4S 5410, 5424, 5430, 5450, 5480, 5470, 5460, NC-5480 Support merged to FOS v7.2: 5431, 6547, M6505 Access Gateway mode is also supported by Fabric OS v7.
Switch operating system version Error numbers and messages received supportSave command output and associated files o For dual CP platforms running FOS v6.
FOS Migration Considerations This section contains important details to consider before migrating to or from this FOS release. FOS Upgrade and Downgrade Special Considerations DCX/DCX-4S units running any FOS v7.1 can be non-disruptively upgraded to FOS v7.2.0d. This upgrade is nondisruptive to both FC and FCoE traffic (when using FCOE10-24 blades). Any firmware activation on Brocade 7800, or DCX, DCX-4S, DCX 8510-8, DCX 8510-4 with FX8-24 will disrupt I/O traffic on the FCIP links.
Important Notes This section contains information that you should consider before you use this Fabric OS release. Brocade Network Advisor Compatibility Brocade Network Advisor greatly simplifies the steps involved in daily operations while improving the performance and reliability of the overall SAN and IP networking environment. Brocade Network Advisor unifies, under a single platform, network management for SAN, LAN and converged networks.
users with versions prior to v12.1.4 and Oracle JRE 1.7.0 update 45 will not be able to launch WebTools from Network Advisor. FOS v7.2.0d is qualified and supported with Oracle JRE 1.7.0 update 25, update 45, and update 51. Users will not see a warning message when WebTools is launched through HTTPS with JRE 1.7.0 update 25 or update 45. Launching WebTools through Brocade Network Advisor is also supported with JRE 1.7.0 update 25 and update 45. Launching WebTools with Oracle JRE 1.7.
Supported Products and FOS Interoperability Brocade 6520 FOS v7.1 or later 5430 FOS v7.1 or later10 5431, 6547, M6505 FOS v7.2 or later10 48000 with FA4-18 blade(s), Brocade 7600 V6.2.2 or later 6 Mi10k, M6140 (McDATA Fabric Mode and Open Fabric Mode) 1 Not Supported Multi-Protocol Router Interoperability Brocade 7500 and FR4-18i blade V6.2.2 and higher 4 6 8 McDATA SANRouters 1620 and 2640 Not Supported NOS (VDX Platform) Interoperability Brocade VDX6710, VDX6720, VDX6730 NOS v2.1.
Patch code levels with full zoning compatibility Main code level FOS v6.2 FOS v6.3 FOS v6.4 FOS v6.2.2d or later FOS v6.3.2a or later FOS v6.4.1 or later If there are switches running FOS versions lower than the above listed patch levels in the same fabric as a switch with FOS v7.0 or later, then cfgsave and cfgenable operations initiated from these switches will fail if the zoning database is greater than 128KB.
BRCD-FCIP-EXT.mib Added support for the following MIB objects at tunnel level in the FCIP Extension tunnel. Until and including 7.1.0 release, the following MIB objects were supported only at connection level. fcipExtendedLinkTcpDroppedPackets fcipExtendedLinkTcpSmoothedRTT fcipExtendedLinkRtxRtxTO fcipExtendedLinkRtxDupAck fcipExtendedLinkDupAck 1.3.6.1.4.1.1588.4.1.1.3 1.3.6.1.4.1.1588.4.1.1.5 1.3.6.1.4.1.1588.4.1.1.9 1.3.6.1.4.1.1588.4.1.1.10 1.3.6.1.4.1.1588.4.1.1.
Fabric OS v7.2 software is fully qualified and supports the blades for the DCX 8510-8 and DCX 8510-4 noted in the table below. DCX 8510-8/DCX 8510-4 Blade Support Matrix FC16-32, FC16-48 16G FC blades FOS v7.0 or later. FC8-64 64 port 8Gbit port blade With any mix and up to 8/4 of each. No restrictions around intermix. Note: FC8-16, FC8-32, FC8-48 blades are not supported on DCX 8510 platforms. FC8-32E, FC8-48E FOS v7.0.1 or later. Intelligent blade Up to a total of 8/4 intelligent blades.
Power Supply Requirements for Blades in DCX/DCX-4S Blades Type of Blade FC10-61, FC816, FC8-32, FC 8-48, FC864 Port Blade FR4-18i1 FS8-18, FX8-24, FCOE10-24 DCX/DCX-4S DCX/DCX-4S @110 VAC (Redundant configurations) @200-240 VAC (Redundant configurations) 2 Power Supplies 2 Power Supplies Intelligent Blade Not Supported 2 Power Supplies Intelligent Blade Not Supported DCX: 2 or 4 Power Supplies Comments DCX-4S: 2 Power Supplies Distribute the Power Supplies evenly to 2 different AC con
Typical Power Supply Requirements Guidelines for Blades in DCX 8510-8 (For specific calculation of power draw with different blade combinations, please refer to Appendix A: Power Specifications in the 8510-8 Backbone Hardware Reference Manual) Configured Number of Ports Blades Type of Blade DCX 8510-8 @110 VAC (Redundant configurations) DCX 8510-8 @200-240 VAC (Redundant configurations) Comments Any combination of 8Gb or 16Gb ports with QSFP ICLs FC8-64, FC16-32, FC8-32E Port Blade 4 Power Supplie
Typical Power Supply Requirements Guidelines for Blades in DCX 8510-8 (For specific calculation of power draw with different blade combinations, please refer to Appendix A: Power Specifications in the 8510-8 Backbone Hardware Reference Manual) Configured Number of Ports Blades Type of Blade DCX 8510-8 @110 VAC (Redundant configurations) DCX 8510-8 @200-240 VAC (Redundant configurations) Comments 384 16Gb ports + QSFP ICLs FC16-32, FC16-48 Port Blade Not Supported 4 Power Supplies 200-240VAC: For
Typical Power Supply Requirements Guidelines for Blades in DCX 8510-4 (For specific calculation of power draw with different blade combinations, please refer to Appendix A: Power Specifications in the 8510-4 Backbone Hardware Reference Manual) Configured Blades Number of Ports Type of Blade DCX 8510-4 @110 VAC (Redundant configurations) DCX 8510-4 @200-240 VAC (Redundant configurations) Comments 96 ports max with QSFP ICLs FC16-32, FC8-32E Port Blade 2 Power Supplies 2 Power Supplies 1+1 redunda
If FOS v7.2 or later is factory installed (or net installed), Adaptive Networking features are always available. This matches the behavior of the Brocade 6520 and all products shipping with prior versions of FOS and with the Adaptive Networking license factory installed. Ports will come up in AE mode by default If the remote port supports QOS and is not explicitly disabled, the link will come up in QOS mode. Otherwise, the link will come up in normal mode.
Gen 5 platforms and blades are capable of setting an EHT value on an individual port basis. On 8G platforms EHT is set on an ASIC-wide basis, meaning all ports on a common ASIC will have the same EHT setting. Extra care should be given when configuring EHT on 8G platforms or Gen 5 platforms with 8G blades to ensure E_Ports are configured with an appropriate Hold Time setting. When using Virtual Fabrics and creating a new Logical Switch when running FOS v7.1.
With Windows and Veritas Volume Manager/Veritas Dynamic Multipathing, when LUN sizes less than 400MB are presented to BES for encryption, a host panic may occur and this configuration is not supported in the FOS v6.3.1 or later release. Hot Code Load from FOS v7.1.x to FOS v7.2 or later is supported. Cryptographic operations and I/O will be disrupted but other layer 2 FC traffic will not be disrupted.
FCoE/DCB/CEE (FCOE10-24) When upgrading a DCX/DCX-4S with one or more FCOE10-24 blades from FOS v6.x to FOS v7.0.0 or later, the user should carefully review Chapter 5 of the FOS v7.0.0 Converged Enhanced Ethernet Administrator’s Guide. Ethernet L2 traffic with xSTP Hello timer set to less than or equal to 3 seconds may experience momentary traffic disruption during HA failover. Hot plugging a CP with firmware level less than FOS v6.3.
are identical this merge logic guarantees uniqueness in any modified login group name (switches with the same OUI will have unique last 3 bytes in WWN). However, if the participating switches have different OUIs but identical last three bytes in the switch WWNs, then the merge logic will fail to guarantee uniqueness of login group names. This will result in one of the login groups being dropped from the configuration.
FL_Port (Loop) Support FL_Port is not supported on FC16-32, FC16-48, FC8-32E, FC8-48E, Brocade 6510, Brocade 6505 and Brocade 6520. The FC8-48 and FC8-64 blade support attachment of loop devices. Virtual Fabrics must be enabled on the chassis and loop devices may only be attached to ports on a 48-port or 64-port blade assigned to a non-Default Logical Switch operating with the default 10bit addressing mode (they may not be in the default Logical Switch).
However, a port may remain in “Port Throttled” state for an extended period of time and may never come online if it fails to negotiate speed successfully with the neighboring port. Users are advised to check the speed setting of the neighboring switch port to determine the cause of the speed negotiation failure. Example Output: 74 9 10 Throttled) 36ed40 id N8 In_Sync FC Disabled (Port Port Mirroring Port Mirroring is not supported on the Brocade 7800.
Zoning Support for up to 2MB zone database in a fabric with only DCX/DCX-4S/DCX8510 systems. The presence of any other platform in the fabric will limit the maximum zone database to 1MB. Please note that there is no enforcement by FOS 7.1 or later to restrict users to operate within a zone database limit - it is the responsibility of the user to not exceed this limit. There are limitations to zoning operations that can be performed from a FOS v6.x switch that is in the same fabric as a FOS v7.
HA failover on DCX/DCX-4S/DCX 8510 platforms while running FOS v7.0 or later firmware Firmware upgrade from v7.0 to a later release on Brocade 300, 5100, VA-40FC, 5300, 6510 Firmware upgrade from v7.0.1 to a later release on Brocade 6505 Firmware upgrade from v7.1.0 to a later release on Brocade 6520 The QSFP information in the sfpshow output will indicate the ID field as all zeros. This is as designed.
Defects Closed with Code Change in Fabric OS v7.2.0d This section lists the defects with Critical, High and Medium Technical Severity closed with a code change as of February 24, 2014 in Fabric OS v7.2.0d. DEFECT000494570 Defect ID: High Technical Severity: FOS Product: FOS7.2.0 Reported In Release: Probability: Medium Technology: Traffic Management Routing Technology Area: Closed In Release(s): Upgrading to FOS7.2.
Closed with Code Change in Fabric OS v7.2.0c This section lists the defects with Critical, High and Medium Technical Severity closed with a code change as of February 5, 2014 in Fabric OS v72.0c. DEFECT000491192 Defect ID: Critical Technical Severity: FOS Product: FOS7.2.0 Reported In Release: Probability: Medium Technology: Traffic Management Routing Technology Area: Closed In Release(s): FOSv7.2.0, 7.2.0a, 7.2.0b, 7.2.0c, 7.2.
Closed with Code Change in Fabric OS v7.2.0b This section lists the defects with Critical, High and Medium Technical Severity closed with a code change as of December 2, 2013 in Fabric OS v7.2.0b.
Closed with Code Change in Fabric OS v7.2.0b Defect ID: DEFECT000472858 Technical Severity: High Summary: A learning flow defined with both generator and monitor as feature options and srcdev "*" specified, monitors only a portion of real flows on the egress port Symptom: A learning flow, defined on an egress port with both generator and monitor features specified and also has either srcdev or dstdev option as '*' will monitor less number of flows than actual number of flows going through the egress port.
Closed with Code Change in Fabric OS v7.2.0b Defect ID: DEFECT000473948 Technical Severity: High Summary: Creating MAPS policy failed with generic error message 'failed to create policy' Symptom: The MAPS policy create failed returning a generic error 'failed to create policy' with no reason why it failed. Probability: Medium Feature: Mgmt Embedded - CAL Function: Other Reported In Release: FOS7.2.
Closed with Code Change in Fabric OS v7.2.0b Defect ID: DEFECT000477049 Technical Severity: Medium Summary: Unable to sort columns in name server section of FOS Web Tools Symptom: Data is not sorted when toggling column headers of the name server section in Web Tools Probability: Medium Feature: WebMgmt Function: Name Server Reported In Release: FOS7.2.0 Fabric OS v7.2.0d Release Notes v1.
Closed with Code Change in Fabric OS v7.2.0a This section lists the defects with Critical, High and Medium Technical Severity closed with a code change as of September 9, 2013 in Fabric OS v7.2.0a Defect ID: DEFECT000433200 Technical Severity: Medium Summary: Switch cannot be managed from WebTools or BNA though management via CLI works. Symptom: Under rare condition management process (HTTPD) gets stuck and switch reports as unreachable via BNA and Webtools.
Closed with Code Change in Fabric OS v7.2.0a Defect ID: DEFECT000465730 Technical Severity: Medium Summary: Enhancement to asic parity error monitoring threshold Symptom: Current default configuration for blade faults is not sensitive enough for some ficon environment setup. Customer may experience IFCCs when there are low level asic parity errors. New CLI options will allow blade to be faulted sooner when there are parity errors. Default threshold is maintained the same as Pre-FOS7.
Closed with Code Change in Fabric OS v7.2.0a Defect ID: DEFECT000468007 Technical Severity: High Summary: Host discovery issues via Ex ports on ICL in multi chassis configuration Symptom: Host may not see all target LUNs in a topology using multi-chassis EX ports on ICL configuration Workaround: Portdisable enable switch ports for affected devices. Probability: Medium Feature: FC Services Function: Name Server Reported In Release: FOS7.2.
Closed with Code Change in Fabric OS v7.2.0a Defect ID: DEFECT000470123 Technical Severity: High Summary: Switch running agshow panics or BNA seed switch panics when polling for AG info in a fabric with AG switches. Symptom: After the port connecting AG to switch bounces, before fabric management server and name server data base are stabilized, polling from BNA caused seed switch to panic, similarly run agshow on switch can cause switch to panic. The timing window for triggering the panic is very small.
Appendix: Additional Considerations for System z (FICON) Environments As noted at the beginning of the release notes, Brocade recommends all customers planning or using previously FICON qualified FOS version 7.2.0b to upgrade to FOS v7.2.0d. New Features Support Not all possible combinations of features and hardware configurations are included in the FICON qualification process. Features and hardware configurations not supported for FICON may be supported for open systems environments.
Area Comments FCIP When performing multiple cabling changes to the SAN fabric in a FICON Emulating FCIP Tunnel configuration with the Brocade 7800 or FX8-24 blade, either disable all of the FCIP Tunnels or issue the switch disable command on all FCIP interconnected switches to avoid IFCCs in a mainframe environment.
Area Comments It is suggested that Port Fencing be used to avoid taking ports down for normal fabric events. The recommended fencing criteria and settings are: Criteria Manageability Value ITW (Invalid Transmission Words) 25 per minute CRC (Cyclical Redundancy Check) 3 per hour Protocol Errors 2 per minute State Change 7 per minute Link Reset 3 per minute Note: Port fencing should not be set for C3 discards. While Port fencing is supported in v7.2.
Maximum CUP Support This table indicates the maximum supported number of logical switches that can have FMS (CUP) enabled on the specified platform. Platform Maximum Number of CUP Instances 8510-8 4 8510-4 4 6510 2 (no base switch) DCX 4 DCX-4S 4 5300 4 7800 2 (no base switch) Interoperability When cascaded to other switches, referred to as a “fabric,” all switches in the fabric must be at FOS v7.1.0c or FOS v7.2.0bi before upgrading to v7.2.0d. Interoperability between switches at FOS v6.
5300 5100 7800 48000 Platforms operating with FOS v7.1.0c can be managed with Brocade Network Advisor v12.1.3. The following platforms are NOT supported for interoperability in fabrics with switches using FOS v7.x: M6140 Mi10K 7500/7500 i Brocade recommends all customers planning or using FICON qualified FOS version 7.2.0b to upgrade to FOS v7.2.0d. Non disruptive firmware upgrade to v7.2.0d for FICON is also supported from FOS v7.1.0c and it is not required to go to FOS v7.2.