HP StorageWorks SAN Director Installation Guide (A7393-90009, May 2007)

SAN Director installation guide 117
Verifying operation of the new CP card
To verify that boot and POST are complete on the new CP card (requires a minimum of three
minutes), and that the CP cards have achieved failover redundancy:
1. Wait until the status LEDs on both CP cards are not lit.
NOTE: The status LEDs on the active CP card lights amber until the active CP card is fully
operational; the status LED on the standby CP card lights amber until the CP cards have achieved
failover redundancy.
2. Login into the active CP card as admin.
3. Enable the redundancy feature by issuing the haEnable command from the serial console for
the active CP card.
4. From the serial console for the active CP card (it should still be the CP card that was not
replaced), issue the haShow command, and verify that the command output shows:
HA Enabled Heartbeat Up
HA-state in sync.
If not, POST is not complete or the CP cards have not yet achieved redundancy. Wait one or two
minutes and re-enter the command, until you can verify that redundancy has been achieved.
NOTE: If haShow indicates any errors after redundancy is achieved, contact HP.