HP StorageWorks SAN Director Installation Guide (A7393-90009, May 2007)

SAN Director installation guide 197
System FRU weights
Facility requirements
The facility where the 4/256 SAN Director is in use must meet the following requirements to provide
for correct operation:
Power requirements for a physical inlet:
Input power requirements: 200-240 VAC, 12A, 50-60 Hz
Recommended power connector: IEC 320, EN60320 C19-Angled, 16A/250VAC
Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the
chassis nameplate
An air flow of at least 350 cubic feet per minute (595 cubic meters per hour), available in the
immediate vicinity of the 4/256 SAN Director
The power specifications listed in Table 50 on page 198
Table 49 System FRU weights
FRU Weight
CP4 card 3.1 kg (6.8 lbs)
FC4-16 port blade 2.7 kg (6.0 lbs) without media
FC4-32 port blade 3.1 kg (6.8 lbs) without media
FC4-48 port blade 3.1 kg (6.8 lbs) without media
FR4-18i port blade 3.36 kg (7.4 lbs) without media
FC4-16IP port blade 3.18 kg (7.0 lbs) without media
Filler panel 1.5 kg (3.2 lbs)
Power supply 3.2 kg (7.0 lbs)
Blower assembly 4.0 kg (8.8 lbs)
Chassis door 3.5 kg (7.6 lbs)
Cable management comb 0.3 kg (0.6 lbs)
WWN bezel 0.3 kg (0.6 lbs)