HP StorageWorks SAN Director Installation Guide (A7393-90009, May 2007)

SAN Director installation guide 43
Two power outlets—Identify one power outlet for each of the two power cords. Installing the
power cords at two separate sources ensures power supply redundancy.
Torque driver—Required to secure the 14U Rack Mount Kit hardware to the rack rails.
Fiber optic protective plugs—For safety and port transceiver protection, fiber optic protective
plugs must be inserted in all 4/256 SAN Director ports without Fiber optic cables attached.
Standard flat-tip and cross-tip Phillips screwdrivers—Required to remove, replace, adjust or
tighten various FRUs, chassis, or rack components.
Electrostatic discharge (ESD) grounding strap—Required when working in and around the switch
card cage. Use the ESD strap supplied with the switch.
Maintenance terminal (desktop or notebook computer)—Required to configure switch network
addresses and acquire event log information through the serial port. Computer requirements
include:
•Microsoft
® Windows® 2000, Microsoft® Windows XP, Microsoft® Windows NT 4.0, or
Windows Millennium Edition
® operating system installed
RS-232 serial communication software (for example, ProComm Plus or HyperTerminal)
HP-supported racks—HP 9,000, HP 10,000 series and HP System/e racks. HP only supports a
maximum of two SAN Director switches in a rack.
Important rack mount safety guidelines
Review the following rack mount guidelines before proceeding with the installation.
WARNING! A fully populated 4/256 SAN Director (384 ports) weighs approximately
216 lbs (96 kg) and requires a minimum of two people and a hydraulic or assisted lift to install it.
Do not use any of the bays (such as the power supply or blower assembly bays) for leverage.
To ensure adequate cooling, install the chassis with the nonport side facing the air-intake aisle. This
prevents the blowers from pulling in heated exhaust air.
If the switch is installed in a cabinet, verify that the cabinet is balanced and secured mechanically
and that the removal and installation procedure will not compromise cabinet stability.
Provide a space that is 14 rack units (14U) high, 29 in. deep, and 19-in. wide. 1U is equal to
1. 75 i n .
Plan to install the 4/256 SAN Director with the nonport side facing the air-intake aisle.