Brocade Fabric OS Message Reference - Supporting Fabric OS v7.0.1 (53-1002448-01, March 2012)

Fabric OS Message Reference 181
53-1002448-01
Chapter
25
EM System Messages
EM-1001
Message <timestamp>, [EM-1001], <sequence-number>, FFDC, CRITICAL, <system-name>, <FRU
ID> is overheating: Shutting down.
Probable Cause Indicates that the specified field-replaceable unit (FRU) is shutting down due to overheating. This
event is typically due to a faulty fan and can also be caused by the switch environment.
Recommended
Action
Verify that the location temperature is within the operational range of the switch. Refer to the
Hardware Reference Manual for the environmental temperature range of your switch.
Execute the fanShow command to verify that all fans are running at normal speeds. If any fans are
missing or are not performing at a high enough speed, they should be replaced.
Severity CRITICAL
EM-1002
Message <timestamp>, [EM-1002], <sequence-number>, FFDC, INFO, <system-name>, System fans
status <fan FRU>.
Probable Cause Indicates that a nonbladed system has overheated and may shut down. All fan speeds are dumped
to the console.
Recommended
Action
Verify that the location temperature is within the operational range of the switch. Refer to the
Hardware Reference Manual for the environmental temperature range of your switch.
Execute the fanShow command to verify that all fans are running at normal speeds. If any fans are
missing or are not performing at a high enough speed, they should be replaced.
Severity INFO
EM-1003
Message <timestamp>, [EM-1003], <sequence-number>, FFDC, CRITICAL, <system-name>, <FRU
ID> has unknown hardware identifier: FRU faulted.
Probable Cause Indicates that a field-replaceable unit (FRU) header could not be read or is not valid. The FRU is
faulted.
Recommended
Action
On Brocade 24000 and 48000, reseat the specified FRU.
If the problem persists, restart or power cycle the switch.