Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers
Appendix A
System Requirements Summary
Power Consumption and Air Conditioning
43
Table A-1 Example Power Consumption (Theoretical Maximum) and Air
Conditioning Requirement Summary
Component Quantity
Multiply
Quantity
By:
Power
Dissipated
(kilowatts)
Air
Conditioning
Required (tons)
(kilowatts/3.517
=tons)
Chassis 1 426 426.00 (.426) 0.121
Cell Board (PA8700) 2 746 1492.00 (1.492) 0.424
PCI Card (Maximum 25W) 16 25 400.00 (.400) 0.114
Power Supply (BPS) 2 125 250.00 (.250) 0.071
DVD 1 20 20.00 (.020) 0.006
Disk Drive 4 25 100.00 (.100) 0.028
Core I/O 2 70 140.00 (.140) 0.040
PCI Power Supply 2 47 94.00 (.094) 0.027
Total 2922.00 (2.922) .831
Table A-2 Power Consumption (Theoretical Maximum) and Air Conditioning
Requirement Summary
Component Quantity
Multiply
Quantity
By:
Power
Dissipated
(kilowatts)
Air
Conditioning
Required (tons)
(kilowatts/3.517
=tons)
Chassis 1 426 426.00 (.426) 0.121
Cell Board (PA8700) 746
PCI Card (Maximum 25W) 25
Power Supply (BPS) 125
DVD 20
Disk Drive 25
Core I/O 70
PCI Power Supply 47
Total