Site Preparation Guide, Second Edition - hp rp7405/rp7410 Servers
Appendix A
System Requirements Summary
Power Consumption and Air Conditioning Requirement
44
Power Consumption and Air Conditioning Requirement
Table A-3 Example Power Consumption (Typical) and Air Conditioning
Requirement Summary
Component Quantity
Multiply
Quantity
By:
Power
Dissipated
(kilowatts)
Air
Conditioning
Required (tons)
(kilowatts/3.517
=tons)
Chassis 1 330 330.00 (0.33) 0.094
Cell Board (PA8700) 2 500 1000.0 (1.00) 0.284
PCI Card (25W max) 16 10 160.00 (0.16) 0.045
Power Supply (BPS) 2 49 98.00 (.098) 0.027
DVD 1 20 20.00 (0.02) 0.006
Disk Drive 2 25 50.00 (0.05) 0.014
Core I/O 2 29 58.00 (0.058) 0.016
PCI Power Supply 2 47 94.00 (0.094) 0.027
Total 1810.00
(1.810)
0.513
Table A-4 Power Consumption (Typical) and Air Conditioning Requirement
Summary
Component Quantity
Multiply
Quantity
By:
Power
Dissipated
(kilowatts)
Air
Conditioning
Required (tons)
(kilowatts/3.517
=tons)
Chassis 1 330 330.00 (0.33) 0.094
Cell Board (PA8700) 500
PCI Card (25W max) 10
Power Supply (BPS) 49
DVD 0
Disk Drive 25
Core I/O 29
PCI Power Supply 47
Total