Installation Guide, Third Edition - Server Expansion Unit

Chapter 4
Cabling and Power Up
Connecting AC Input Power
80
Connecting AC Input Power
The Server Expansion Unit has two line cord configurations:
The preferred configuration is line cords B0 and A0 plugged into the Server Expansion Unit. This
configuration provides power supply redundancy when each power cord is plugged into a different power
source.
The other configuration is line cord A0 plugged into the Server Expansion Unit. Use the A0 power cord
receptacle when only one power source is available to supply power to the Server Expansion Unit.
Figure 4-38 Power Cord Receptacle Configuration
Power cord receptacles are identified using a label at the rear side of the chassis indicating which receptacle
is B0 and which receptacle is A0.
The Server Expansion Unit follows the power configuration that is selected for the server. So, if grid A0 & B0
are selected for the server, the Server Expansion Unit needs to have both power cords connected. Otherwise,
power fault messages are logged. You cannot select one power configuration for the Server Expansion Unit
and another power configuration for the server.
NOTE If only one power cord receptacle is used, always plug the power cord into A0.
B0 A0