Site Preparation Guide, Third Edition - Server Expansion Unit
Appendix A
General Site Preparation Guidelines
Sample Site Inspection Checklist
37
7. Are there channels or cutouts for cable routing?
8. Is there a network line available?
9. Is a telephone line available?
10. Are customer supplied peripheral cables and
LAN cables available and of the proper type?
11. Are floor tiles in good condition and properly
braced?
12. Is floor tile underside shiny or painted? If
painted, judge the need for particulate test.
Power and lighting
Number Area or condition Yes No
13. Are lighting levels adequate for maintenance?
14. Are there AC outlets available for servicing
needs? (for example, laptop)
15. Does the input voltage correspond to equipment
specifications?
15A Is dual source power used? If so, identify types
and evaluate grounding.
16 Does the input frequency correspond to
equipment specifications?
17. Are lightning arrestors installed inside the
building?
18. Is power conditioning equipment installed?
19. Is there a dedicated branch circuit for
equipment?
20. Is the dedicated branch circuit less than 75 feet
(22.86 meters)?
21. Are the input circuit breakers adequate for
equipment loads?
Safety
Number Area or condition Yes No
22. Is there an emergency power shutoff switch?
23. Is there a telephone available for emergency
purposes?
Table A-6 Site Inspection Checklist (Continued)
Please check either Yes or No. If No, include comment number or date
Comment
or Date