Redundant PDU High-Line Example #1
This example presents a high-line configuration for PDU redundancy supporting one to three
enclosures. Figure 13 is valid for high-line PDUs with inputs rated 16 A. It does not support four
enclosures at high-line voltage because the total current load of 4 * 5 A = 20 exceeds the input
rating of 16 A. See the previous restrictions.
Figure 13. High-line redundant PDU configuration supporting one to three enclosures
Redundant PDU High-Line Example #2
This example presents a high-line configuration for PDU redundancy supporting one to four
enclosures. Figure 14 is valid for high-line PDUs with inputs rated 24/30/32 A. It does not
support five enclosures at high-line voltage because the total current load of 5 * 5 A = 25 exceeds
the input rating of 24 A. See the previous restrictions.
Figure 14. High-line redundant PDU configuration supporting one to four enclosures