HP BladeSystem c3000 Enclosure and c3000 Tower Enclosure Maintenance and Service Guide

Cabling 63
Allow any active Onboard Administrator module to access the linked enclosures.
Use the enclosure link-up port ("Enclosure rear components" on page 75) on the top enclosure for
temporary connection to a PC using the enclosure service port ("Cabling a PC to the enclosure service
port" on page 65) to provide quick access to any Onboard Administrator module, iLO, or interconnect
module with Ethernet management ability.
Allow enclosure settings to be shared between enclosures, which simplifies deployment of multiple
enclosures.
NOTE: The enclosure link ports are designed only to support c-Class enclosures in the same rack.
The enclosure link-up port on the top enclosure is the service port, and the enclosure link-down port
on the bottom linked enclosure is unused.
NOTE: If more c-Class enclosures are added to the rack at a later time, the open enclosure link-up
port on the top enclosure can be used to link the new enclosure.
NOTE: The HP BladeSystem c-Class enclosure link ports are not compatible with the HP
BladeSystem p-Class enclosure link ports.
To link the enclosures, use a standard Category 5 (CAT5) patch cable to connect the enclosure link-down port
on the first enclosure to the enclosure link-up port on the second enclosure.
KVM module cabling
For local access to the enclosure:
1. Connect a monitor to the video connector on the c3000 KVM module.