HP BladeSystem c3000 Enclosure Quick Setup Instructions
8
If the empty bays are configured for a full-height device, join two
device bay blanks to create a full-height blank.
Installing the rear components
CAUTION: To prevent improper cooling and thermal
damage, do not operate the enclosure unless all bays are
populated with a component or a blank.
1. Slide the fan into the enclosure until it locks in place.
NOTE: The HP BladeSystem c3000 Enclosure ships with
four HP Active Cool 100 fans and supports up to six fans.
Install fans based on the number of storage or server
blades installed:
• For one to four half-height storage or server blades or
one to two full-height storage or server blades, install
four fans in bays 2, 4, 5, and 6.
• For additional storage or server blades, install six fans
using all bays.
NOTE: You cannot install HP Active Cool 100 fans and
HP Active Cool 200 fans in the same enclosure. The
Onboard Administrator sends an error message, and you
must remove the type of fan with the least number of units
installed.
NOTE:
When installing a fan in the top row of fan bays,
orient the fan so that the LED is in the lower right corner.
When installing a fan in the bottom row of fan bays, orient
the fan so the LED is in the upper left corner.
2. (Optional) Slide the c3000 KVM module into the bay. When fully
inserted, the device locks into place.
3. Slide the power supply into the power supply bay until the device
locks into place.