HP BladeSystem c3000 Enclosure Quick Setup Instructions

9
WARNING: A risk of electric shock from high leakage
current exists. Before connecting the AC supply to the
power enclosures, be sure that the electrical outlets are
properly grounded (earthed).
When installed in a rack, the enclosure must be used with
an internal rack mount power distribution unit (PDU) or
uninterruptible power supply (UPS) that uses an industrial
style wall plug (for example, locking type NEMA or IEC
309 pin and sleeve configuration) which insures a reliable
protective earth ground connection.
When installed in a rack-free environment, the area must
be designated as a restricted access area, and the
enclosure must be used with a dedicated uninterruptible
power supply (UPS) that uses an industrial style wall plug
(for example, locking type NEMA or IEC 309 pin and
sleeve configuration) which insures a reliable protective
earth ground connection.
Installation and maintenance must be performed by
trained service personnel.
NOTE: When installing a power supply in power supply
bay 1, 2, or 3, orient the power supply so the plug is on the
left side. When installing a power supply in power supply
bay 4, 5, or 6, orient the power supply so the plug is on the
right side.
For AC redundant (N+N power supplies) configurations, an
even number of power supplies is required. For this
configuration, where N is the number of power supplies being
used, populate the power supply bays as shown.
N + N Populate the following power supply bays
1 + 1 1 and 4
2 + 2 1, 2, 4, and 5
3 + 3 Populate all bays
For power supply redundant (N+1 power supplies)
configurations, where N is the number of power supplies being
used, populate the power supply bays as shown.
N + 1 Populate the following power supply bays
1 + 1 1 and 4
2 + 1 1, 4, and 2
3 + 1 1, 4, 2, and 5
N + 1 Populate the following power supply bays
4 + 1 1, 4, 2, 5, and 3
5 + 1 Populate all bays
4. Slide the enclosure/Onboard Administrator link module into the
bay until the device locks into place.
Connecting the cables
1. Identify all connectors.
Item Connector Description
1
Enclosure
link-down
port
Connects to the enclosure link-up port on the
enclosure beneath it with a CAT5 patch cable.
2
Enclosure
link-up
port and
service
port
Connects to the enclosure link-down port on the
enclosure above it with a CAT5 patch cable. On
a stand-alone enclosure or the top enclosure in a
series of linked enclosures, the top enclosure
link-up port can function as a service port.