HP BladeSystem c3000 Tower Enclosure Setup and Installation Guide

Using the HP BladeSystem Insight Display 49
o
None
Power Limit—The default setting is Not Set. The Power Limit Watts AC setting can be changed in
increments of 50 Watts.
IMPORTANT: When calculating the Power Limit Watts AC value, derate the circuit to 80% of
the maximum to prevent tripping the circuit breaker (United States only).
IMPORTANT: If your facility cannot support the calculated peak Watts AC, set the Power
Watts AC value to match the capability of your facility.
Dynamic Power—The default setting is Enabled. The following selections are valid:
o Enabled—Some of the power supplies can be automatically placed on standby to increase
overall enclosure power subsystem efficiency.
o Disabled—All power supplies share the load; the power subsystem efficiency will vary based on
load.
OA1 IP Addr—The default setting is DHCP; if no IP address is received, the IP address is 0.0.0.0.
The IP address, mask, and gateway are set within this option.
OA2 IP Addr—If this module is present, the default setting is DHCP; if no IP address is received, the
IP address is 0.0.0.0. If only one Onboard Administrator module is installed, the screen will display
"Not Present."
Enclosure Name—The default setting is a unique factory-assigned name. The accepted character
values are 0–9, A–Z, a–z, -, _ and
. is used to signal the end of the name.
NOTE: Do not use the symbol in the middle of a text field. Entries in text fields will be
truncated to the last character before the
symbol.
TIP: Select Clear from the navigation bar to quickly clear entries in text fields up to the
symbol.
Rack Name—The default setting is UnnamedRack The accepted character values are 0–9, A–Z, a–z,
-, _ and
. is used to signal the end of the name.