ProCurve 1U Rack Mount Bracket Installation Guide

The fasteners specified in Table 1-1.
Table 1-1 Fasteners
DescriptionTorqueFormatSizeQuantity
Rack mount bracket mounting screw (flat-head).15 in-lbPhillips
(Posidrive)
M4 x 8 mm8
Slide bracket mounting screw location A (rear
column) and location B (front column).
30 in-lbPan Head XRCS10–32 x 0.6258
Cage nut for 10–32 machine screw. A square nut
that clips into the rack column.
N/ASquare Nut10–32 Cage
Nut
4
Washer to align screw in square hole.N/AAlignment
Washer
#104
Packaging and documentation.
The bracket hardware shown in Figure 1-1.
Figure 1-1 ProCurve 1U Rack Mount Bracket Hardware
1
2
The ProCurve 1U rack mount bracket is used in HP Cluster Platform configurations, however,
it might be adapted to other HP Cluster Platform rack mount applications (see the installation
documentation for your hardware).
The following list corresponds to the callouts shown in Figure 1-1:
1. Two rack mount brackets, one shown
2. Two slide brackets, one shown
To prevent screws from becoming loose because of vibration, HP recommends that you use an
adjustable torque drive, set to the torque specifications given in the table above. Contact your
HP sales representative if any parts are missing or damaged.
1.6 Required Resources
To install the ProCurve 1U rack mount bracket, you require the following resources:
Tools:
— Screwdriver, #2 (medium) Phillips.
— Flat-bladed screwdriver.
4 Preparing for Installation