HP Cluster Platform Workgroup System Tower Hardware Installation Guide
A Workgroup System Tower High-Line Power Examples
Warning!
Be sure that all circuit breakers are locked in the off position before connecting any power
components.
Caution:
HP recommends that no more than two power supplies be plugged into a single power strip.
Important:
The configurations shown in this appendix are examples only and do not show all possible
combinations of PDUs, UPS, and power cords. C20-C13 power cords are not supplied by HP. If
you intend to use the configuration examples with C20-C13 power cords, HP recommends that
you check on the availability of the C20-C13 power cords with an HPC-certified reseller when
you order the Workgroup System Tower.
This appendix provides six different power examples for the Workgroup System Tower, as
follows:
• Example Configuration 1 (4kVA, N+N redundant enclosure with two 32A International
PDUs)
• Example Configuration 2 (2.7kVA, N+N redundant enclosure with two 16A PDUs)
• Example Configuration 3 (3kVA, N+1 redundant enclosure with a 16A PDU)
• Example Configuration 4 (5kVA - 7kVA, N+1 redundant enclosure with a 32A International
PDU)
• Example Configuration 5 (5kVA, N+N redundant enclosure with a 16A 3-Phase PDU)
• Example Configuration 6 (5kVA, N+1 redundant enclosure with a 16A 3-Phase PDU)
Figure A-1 provides an example of a 4kVA, N+N redundant enclosure with a 32A International
PDU (252663-B31 IEC 309-32A). The extension bars are used to allow other devices to be plugged
in.
31