HP StoreOnce B6200 Installation Planning and Preparation Guide (EJ022-90995, November 2013)

Table 5 Weight specifications with modular PDUs, Rack 2
40A24A and 32A
lbskgslbskgs
604.18274.74640.19291.06Single couplet
1000.19454.741036.19471.06Single couplet with maximum storage added
864.98393.28900.98409.60Two couplets
1661.38755.281697.38771.60Two couplets with maximum storage added to couplets
Power/PDU requirements
Two power outlets are required for each couplet. But it is strongly recommended that each rack
be installed with four outlets to allow for ease of expansion, even if the rack has only one couplet.
IMPORTANT: If only two PDUs are connected on a single couplet configuration, they must be
connected to the relevant connection on each side of the rack. If not, and power is applied to only
one side of the rack, then only half of the power supplies on the hardware will be powered on.
Power specification
The power factor is close to unity.
Miniature Circuit Breakers (MCBs), type C, are required to prevent tripping with the initial power
on surge of the racks.
Table 6 Power specification at 220V, single rack installed
BTU/hourAVWASingle rack configuration
6817.431931.461883.608.701 couplet with minimum storage
11435.623192.783113.6014.441 couplet with maximum storage
12240.853505.353418.4415.852 couplets with minimum storage
21477.246027.995878.4427.312 couplets with maximum storage
Table 7 Power specification at 220V, both racks installed
BTU/hourAVWA2–rack configuration
20428.285788.975645.3426.073 couplets with minimum storage
34282.869572.939335.3443.273 couplets with maximum storage
25851.717362.867180.1833.214 couplets with minimum storage
44324.4812408.1412100.1856.154 couplets with maximum storage
Table 8 Power specification at 240V, single rack installed
BTU/hourAVWASingle rack configuration
6810.291951.471880.788.061 couplet with minimum storage
11428.483227.763110.7813.381 couplet with maximum storage
12226.573541.893413.5414.682 couplets with minimum storage
21462.966094.455873.5425.312 couplets with maximum storage
Power/PDU requirements 9