HP FlexFabric 11900 2400W DC Power Supply User Guide-APW100

4
Item Specifications
Humidity
Operating
humidity
(noncondensing)
10% to 95%
Storage humidity
(noncondensing)
5% to 95%
Power supply configuration
You can determine the number of power supplies to be configured for the system
according to the actual power consumption and power supply conditions.
In an environment with two mains power inputs, you can configure N+N redundant
mode.
In an environment with only one mains power input, you can configure N+1 or N+N
redundant mode.
For easy usage and maintenance, configure a proper circuit breaker for each power
input. The rated current of the circuit breaker must be more than 80 A.
NOTE:
In the terms
N+1
and
N+N
, the value of N depends on the number of power supply
slots in the device. N+1 or N+N must not be more than the total number of power
supply slots.
Installing and removing a power supply
Installing a power supply
Figure 2 illustrates the flow for installing a power supply. Strictly follow the sequence to
avoid possible dangers.