HP FlexFabric 11900 2400W DC Power Supply User Guide-APW100
4
Item Specifications
Humidity
Operating
humidity
(noncondensing)
10% to 95%
Storage humidity
(noncondensing)
5% to 95%
Power supply configuration
You can determine the number of power supplies to be configured for the system
according to the actual power consumption and power supply conditions.
• In an environment with two mains power inputs, you can configure N+N redundant
mode.
• In an environment with only one mains power input, you can configure N+1 or N+N
redundant mode.
• For easy usage and maintenance, configure a proper circuit breaker for each power
input. The rated current of the circuit breaker must be more than 80 A.
NOTE:
In the terms
N+1
and
N+N
, the value of N depends on the number of power supply
slots in the device. N+1 or N+N must not be more than the total number of power
supply slots.
Installing and removing a power supply
Installing a power supply
Figure 2 illustrates the flow for installing a power supply. Strictly follow the sequence to
avoid possible dangers.