Site Preparation Guide, Third Edition - HP Integrity cx2600
System Specifications
Electrical Specifications
Chapter 2
14
Electrical Specifications
This section provides electrical specifications for the hp Integrity cx2600 Server.
Grounding
The site building shall provide a safety ground/protective earth ground to all cabinets. A chassis ground point
is provided on the server rear panel. (See Figure 2-2.)
Figure 2-2 Chassis Ground Lug
Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the
branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing
conductor is to be connected from the unit to the building installation earth or, if supplied by a separately
derived system, at the supply transformer or motor-generator set grounding point.
Disconnect Device and Branch Circuit Protection
WARNING Failure to provide an appropriate disconnect device and branch circuit protection
may endanger service personnel. Serious injury and equipment damage may result
if this warning is not observed.
chasgndlug
Chassis
Ground
Lug