Site Preparation Guide, Third Edition - HP Integrity cx2600
System Specifications
Electrical Specifications
Chapter 2
15
A suitable disconnect device must be provided as part of the building installation. The purpose of the
disconnect device is to provide an easy and accessible means for removing power from the product for
servicing.
A suitable branch circuit protection device must be provided as part of the building installation. The purpose
of branch circuit protection is to limit current in the case of a fault.
The disconnect device may also provide branch circuit protection (for example, a circuit breaker). Alternately,
separate disconnect and branch circuit protection devices (fuses and a disconnect switch) may be employed.
The devices must be rated based on the plate rating of the product in accordance with the applicable local
codes and specific customer requirements. Branch circuit protection is commonly selected based on 125% of
the product input rating. Such derating is to avoid nuisance tripping due to load surges or power transients
and to meet code requirements. Applicable codes and customer requirements will vary.
System Power Specifications
Table 2-3 and Table 2-4 list the power specifications for the hp Integrity cx2600 Server. These tables provide
information to help determine the amount of power needed for your computer room.
Table 2-3 System Power Specifications
Specification Value
Nominal Input Voltage –48VDC (–40 to –60 VDC)
Minimum Operating Voltage –36 VDC
Maximum Operating Voltage –72 VDC
Input Current 12A DC typical (with V
IN
–48 VDC)
Input Power 580W typical (@ 85% efficiency)
Maximum Inrush Current 25 A
Maximum Output Current from each
Power Supply
49A DC for the 12V output
3.5A DC for the V3.3sb output
Efficiency 82% (minimum)
Table 2-4 System Power Requirements
Power Required Watts Comments
Maximum configuration
a
a. Maximum power is the sum of the worst case power consumption values of every
subsystem in your hp Integrity cx2600 Server. These worst case values should be used
to calculate the worst case power consumption for your facility installation.
650 Maximum Theoretical
Typical configuration 580