Site Preparation Guide, Third Edition - HP Integrity cx2600
General Site Preparation Guidelines
Facility Characteristics
Chapter 3
35
Windows
Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems.
Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight
places an additional load on the cooling system.
Concentrated load
b
1250 lb (567 kg)
Ultimate load 4,000 lb (1814 kg) per panel
Rolling load 400 lb (181 kg)
Average floor load 500 lb (227 kg)
a. From Table 3-2 on page 34.
b. With 0.08 in. (0.2 cm) of span maximum deflection.
Table 3-3 Typical Raised Floor Specifications (Continued)
Item
a
Rating