Site Preparation Guide, Second Edition - HP Integrity cx2620 Server

A Physical and Environmental Specifications
Table A-1 provides temperature and airflow information for minimum, typical, and maximum
configurations for the server. It also lists the server and rack weights and dimensions. Use this
table as a convenient point of reference.
Table A-1
Overall
System
(W x D x H)
Weight
Condition
Airflow, Maximum at
35ºC
1
Airflow, Nominal
Typical
Heat
Release
RackRackServer
Voltage
-40 to -60
Vdc
W: 44.5 cm
(17.5 in)
D: 50.8 cm
(20 in)
H: 17.8 cm
(7 in)
31.75 kg
(70 lb)
28.1 kg -
31.75 kg
(62 lb - 70
lb)
367 m³/hr216 CFM302 m³/hr178 CFM
340 Watts
Minimum
Config.
650 Watts
Maximum
Config.
580 Watts
Typical
Config.
One CPU, one power
supply,
2
1 GB DIMM,
one DVD or one
CD-RW/DVD, zero
PCI–X cards, one HDD.
Minimum
Config.
Air Flow Diagram Cooling Scheme (F - R)
Front to Rear (F-R)
ASHRAE
Class 1
Two CPUs, two power
supplies, 32 GB DIMMs,
one DVD or one
CD-RW/DVD,fourPCI–X
card, three HDDs.
Maximum
Config.
One CPU, two power
supplies, 12 GB DIMMs,
one DVD or one
CD-RW/DVD,two PCI–X
cards, two HDDs.
Typical
Config.
1 Derate maximum dry bulb temperature 1oC/300 m above 900 m.
2 While only one power supply can be used, N+1 redundancy requires that a second power supply be installed.
49