User Service Guide, Third Edition - HP Integrity cx2620 Server

Table 5-18 Relay Signals
DescriptionAbbreviationSignal
This signal must be pulled up to no more than 24V above Return external
to the system.
When the alarm is not activated, this signal is open (electrically high since
pulled up externally).
When the alarm is activated, this signal is connected by a dry contact
relay to the Return pin.
The external pull-up resistor must limit the current to no more than 1 Amp.
(NO)Normally Open
This signal must be pulled up to no more than 24V above Return external
to the system. When the alarm is not activated, this signal is connected by
a dry contact relay in the system to the Return pin. When the alarm is
activated, this signal opens (electrically high since pulled up externally).
The external pull-up resistor must limit the current to no more than 1 Amp.
(NC)Normally Closed
This is the return path for both the Normally Open and Normally Closed
signals.
(COM)Return
DB9 Pin-Out
Table 5-19 lists the assigned relay, pin number, alarm, and signal name for each pin of the DB9
connector.
Table 5-19 Relay Numbering
SignalAlarmPin #Relay
ALARM0_NOCritical Normally_Open1K1
ALARM0_NCCritical Normally_Closed2
ALARM0_COMCritical Return6
ALARM1_NOMajor Normally_Open7K2
ALARM1_NCMajor Normally_Closed8
ALARM1_COMMajor Return3
ALARM2_NOPower Normally_On4K3
ALARM2_NCPower Normally_Off5
ALARM2_COMPower Return9
Figure 5-3 shows the DB9 pins.
150 Troubleshooting