NonStop NS-Series Planning Guide (H06.03+)
Planning for LAN Communications
HP Integrity NonStop NS-Series Planning Guide—529567-004
6-7
System-Up Dedicated Maintenance LAN
One possible fault-tolerant configuration is a pair of G4SAs (each in a different IOAM
module) with a maintenance LAN connected to the A port on each G4SA. The B port is
then available to support the SWAN LAN.
System-Up Dedicated Maintenance LAN
When the system is up and the OS running, the ME connects to the NonStop
NS-series system’s dedicated maintenance LAN using one of the PIFs on each of two
G4SA adapters. This connection enables OSM Service Connection and OSM
Notification Director communication for maintenance in a running system.
For fault-tolerant dedicated maintenance LAN, two G4SAs are required with one
connected to each ServerNet fabric, X and Y. These G4SA can reside in modules 2
and 3 of the same I/O adapter module (IOAM) enclosure or in module 2 of one IOAME
and module 3 of a second IOAM enclosure. When the G4SA provides connection to
the dedicated maintenance LAN, use the slower 10/100 Mbps PIF A rather than one of
the high-speed 1000 Mbps Ethernet ports of PIF C or D.
If NonStop S-series I/O enclosures are connected to the system, one G4SA can reside
in either module 2 or 3 of an IOAM enclosure and in a NonStop S-series EtherNet
adapter (such as an E4SA, FESA, or GESA) in either slot 53 or 54 of the NonStop
S-series I/O enclosure. When installing EtherNet adapters for the dedicated
maintenance LAN in an Integrity NonStop NS-series IOAM enclosure and in a NonStop
S-series I/O enclosure, it is important that each EtherNet adapter connect to the X and
Y ServerNet. For information about the NonStop S-Series I/O enclosure and the
EtherNet adapters that can be installed in it, see the NonStop S-Series Planning and
Configuration Guide.
Maintenance LAN Links With One IOAM Enclosure
This illustration shows the dedicated maintenance LAN cables connected to the
G4SAs in slot 5 of both modules of an IOAM enclosure and to the maintenance switch:
VST340.vsd
Module 2
Module 3
Maintenance Switch
IOAM
Enclosure
(Group
110)
G4SA EtherNet
PIF Connectors
Cable To
Maintenance
Switch
B
A
C
D