Power and Lighting
Power and Lighting
Section B: Power and Lighting
Yes No RISK
B-1 Are lighting levels adequate for safe maintenance?
Observe behind equipment rows, particularly those adjacent to
walls.
? ? ?
B-2 Does the customer intend to dual source AC input?
(2 power sources, etc.) Ensure the customer is aware that
sources need to be referenced together for maximum
reliability?
? ? ?
B-3 Are outlets available for the new or relocated equipment at the
designated locations?
? ? ?
B-4 Are there extra outlets for support H/W, NSC workstation, laptop,
etc.?
? ? ?
B-5 Do output voltages correspond to equipment specifications?
(see Product Specifications)
? ? ?
B-6 Are the input circuit breakers adequate for equipment loads?
(see Product Specifications)
? ? ?
B-7 Does the input frequency correspond to equipment specifications?
(see Product Specifications)
? ? ?
B-8 Is there a dedicated UPS to power equipment?
(Site wide only, not Standalone)
? ? ?
B-9 Does the customer intend to use standalone UPS devices in addition
to a site wide UPS?
HP does not recommend powering one UPS from another.
? ? ?
B-
10
Is there a dedicated branch circuit for each input to the new or
relocated equipment
? ? ?
B-
11
Are all recepticals either standard or isolated gournd?
All standard receptacles are preferred. Mixing is not
recommended. We only support the use of isolated grounding in
hospital applications.
? ? ?